Servo Controlled Automatic Voltage Stabilizers |
|
| |
|
|
| |
Specification Capacity |
|
|
| |
1KVA to 2000 KVA (Single Phase)
|
|
| |
5
KVA to 1000 KVA (Three Phase) |
|
| |
|
|
| |
Input Voltage Range |
|
| |
180-270V, 160-270V, 140-270V (Single Phase) |
|
| |
340-460V, 300-460V, 280-460V (Three Phase) |
|
| |
Or
any other range as required by you. |
|
| |
|
|
| |
Output Voltage |
|
| |
230V ± 1 % (Single Phase) |
|
| |
400
± 1 % (Three Phase) |
|
| |
or
as desired |
|
| |
Cooling |
- Natural
Air/Oil cooled |
|
| |
Frequency |
- 47-53
Hz |
|
|
|
|
| |
Correction Speed |
- 10-35V Per second |
|
| |
Response Time |
- < 10ms |
|
| |
Waveform Distortion |
- None added by
the |
|
| |
|
equipment |
|
| |
Duty Cycle |
- Continuous |
|
| |
Power Factor |
- Suitable for
all power |
|
| |
|
factor
loads |
|
| |
|
|
|
| |
Optional Facility |
|
| |
- Cut off at two low/ two
high of input voltage
- Overload Protection
- Single-phase Prevention
- By-pass Arrangement
- Surge Suppressor
|
|
| |
|
|
|
| |
Type SE - 15-1 |
|
| |
Single Phase Servo-Controlled Voltage Stabilizer. Suitable
for use with single phase equipment.
|
|
| |
|
|
| |
Type SE - 15-3U |
|
| |
Three-phase Servo-Controlled Voltage Stabilizer. Recommended
for use with unbalanced input supply voltage and/or unbalanced
loads.
It consists of three single phase units connected in star.
Each unit has a motorized single phase variac and a series
transformer. Voltage of each phase is independently sensed
and corrected to the desired value.
These units are, therefore, suitable for use with unbalanced
input supply voltages and unbalanced loads.
|
|
| |
|
|
| |
Type SE - 15-3B |
|
| |
Three-phase
Servo-Controlled Voltage Stabilizer. Recommended for use where
3-phase input supply and load are balanced i.e. all line voltages
and currents are same.
This regulator employs a three phase variable transformer
(3 nos. of single phase variable transformers mechanically
coupled) driven by a single servo motor and three-phase series
transformers. The Output voltage between 'R&Y' phase is
sensed and all the three phase output are corrected accordingly.
These units are, therefore, suitable only for use with balanced
3-phase mains supply. If balanced mains supply cannot be ensured,
TYPE SE - 15-3U should be used.
|
|
| |
|
|
|
| |
Benefits |
|
| |
- Reduces
/ eliminates failure rate of electrical appliances.
-
Increased productivity
-
Reduction in power consumption
-
Reduces wastage of goods in process industry
-
Depreciation from Income Tax
|
|
| |
|
|
| |
Applications |
|
| |
- CNC based machines
- Chemical / Oil Industry
- Information Technology Industry
- Medical Equipment
- Communication & Broadcasting
System
- Airconditioning Plant
- Textile industru
- Cement Plant
- Rolling Steel Mill
- Rubber / Shoe Industry
- Food processing Industry
- Printing and Packaging Industry
- Commercial Building / Complex
- Industrial / Residential
Mainline
|
|
| |
|
|
|
| |
|
|
| |
|
|
|
| |
|
|
|